connection). The County shall reserve the right to require a simple sketch of<br />

a residential building <strong>sewer</strong> from a property owner if deemed necessary.<br />

The County shall reserve the right to require professionally drawn plans <strong>and</strong><br />

specifications <strong>for</strong> any proposed sanitary <strong>sewer</strong> installation when the Sanitary<br />

Engineer <strong>and</strong>/or Ohio E.P.A. deems it necessary.<br />

Basic in<strong>for</strong>mation that shall be shown on all plan/profile <strong>and</strong> specifications<br />

improvement drawings:<br />

1. Proposed sanitary <strong>sewer</strong> mains <strong>and</strong> appurtenances locations.<br />

2. Existing sanitary <strong>sewer</strong> mains <strong>and</strong> appurtenances locations.<br />

3. Detail of proposed sanitary <strong>sewer</strong> connection to the existing sanitary<br />

<strong>sewer</strong>.<br />

4. All utilities shall be shown on the improvement drawings.<br />

5. Manhole detail w/chimney seals requirement.<br />

6. Service connection detail.<br />

7. Pump station, air release manhole, or other <strong>sewer</strong> appurtenance detail,<br />

if applicable.<br />

8. Granular bedding <strong>and</strong> backfill requirements.<br />

9. Other in<strong>for</strong>mation as deemed necessary <strong>and</strong> noted during the O.C.S.E.<br />

review process.<br />

Additional Improvement Drawing In<strong>for</strong>mation:<br />

1. Using cleanouts in lieu of a manhole at the end of sanitary <strong>sewer</strong><br />

extensions shall be subject to the approval of the Sanitary Engineer.<br />

2. Service connections <strong>for</strong> single family dwellings shall not enter manholes<br />

unless otherwise approved by the Sanitary Engineer.<br />

3. Service connections shall be extended from the sanitary <strong>sewer</strong> main to the<br />

property lines or edge of easement areas. Service connections shall be<br />

extend beyond all other utilities by at least three (3) feet.<br />

4.2.0 DESIGN/PLAN <strong>and</strong> SPECIFICATIONS REVIEW PROCESS<br />

The following is a general overview of the O.C.S.E. plan review <strong>and</strong> approval<br />

process:<br />

A. A preliminary plat <strong>and</strong>/or design plans shall be submitted by the<br />

developer or Ottawa Regional Planning Commission, if applicable, to<br />

the O.C.S.E. <strong>for</strong> preliminary review, comment, <strong>and</strong> approval.