3<br />

Installation site preparation<br />

CAUTION<br />

For the DC input circuit (DC power supply part number RPS9-DC), make sure there is a Listed 20<br />

amp circuit breaker, minimum 48Vdc, double pole, on the input to the power supply. The input<br />

wiring for connection to the product should be Listed copper wire, 12 AWG, marked VW-1, <strong>and</strong><br />

rated minimum 90 C.<br />

CAUTION<br />

For a DC system (DC power supply part number RPS9-DC), use a grounding wire of at least 6<br />

American Wire Gauge (AWG). The 6 AWG wire should be attached to an agency-approved crimp<br />

connector, crimped with the proper tool.<br />

Installation site preparation<br />

Cabling infrastructure<br />

Ensure that the proper cabling is installed in the site. Refer to “<strong>Hardware</strong> specifications” on<br />

page 85 or www.brocade.com for a summary of supported cabling types <strong>and</strong> their specifications.<br />

DANGER<br />

The intra-building ports of the equipment or subassembly is suitable for connection to<br />

intra-building or unexposed wiring or cabling only. The intra-building ports of the equipment or<br />

subassembly MUST NOT be metallically connected to interfaces that connect to the OSP or its<br />

wiring. These interfaces are designed for use as intra-building interfaces only (Type 2 or Type 4<br />

ports as described in GR-1089-CORE, Issue 4) <strong>and</strong> require isolation from the exposed OSP<br />

cabling. The addition of Primary Protectors is not sufficient protection in order to connect these<br />

interfaces metallically to OSP wiring.<br />

Installation location<br />

Before installing the device, plan its location <strong>and</strong> orientation relative to other devices <strong>and</strong><br />

equipment. Allow at least 3 in. of space at the front of the device for the twisted-pair, fiber-optic,<br />

<strong>and</strong> power cabling. Also, allow a minimum of 3 in. of space between the sides <strong>and</strong> the back of the<br />

device <strong>and</strong> walls or other obstructions.<br />

A <strong>Brocade</strong> device is suitable for installation in Network Telecommunications facilities <strong>and</strong> locations<br />

where the NEC (National Electric Code) apply.<br />

The device must be installed in a restricted access location, either a Central Office or<br />

customer-premises equipment location.<br />

30 <strong>Brocade</strong> NetIron <strong>CES</strong> <strong>and</strong> <strong>Brocade</strong> NetIron <strong>CER</strong> <strong>Devices</strong> <strong>Hardware</strong> Guide<br />