5.2.4. Rubber Seal Lock Joint (RSLJ) without pipe stop<br />

To assemble a rubber ring joint use this manual. For marking the depth<br />

of entry on the spigot end use the instruction below.<br />

Fig. 5.2.h.<br />

pipe with<br />

integral socket end<br />

rubber ring<br />

locking strip<br />

Mark the depth of entry on the spigot end. The measurement of the mark on the spigot end is in table 5.b.<br />

Table 5.b.<br />

L 2<br />

L mark<br />

mark<br />

stop<br />

collar<br />

Wavistrong <strong>Installation</strong> <strong>Manual</strong><br />

19<br />

insert hole<br />

for locking strip<br />

Fig. 5.2.i.<br />

pipe with spigot end<br />

PN Angular<br />

ID ≤16 bar 20 bar ≥ 25 bar deflection<br />

(mm) Lmark L2 Lmark L2 Lmark L2<br />

RSLJ<br />

(mm) (mm) (mm) (mm) (mm) (mm)<br />

80 96 65 1°30<br />

100 96 65 1°30<br />

150 125 84 125 84 1°30<br />

200 134 94 134 94 165 117 1°30<br />

250 185 127 185 127 229 163 1°30<br />

300 191 133 191 133 245 174 1°30<br />

350 195 138 240 171 240 171 1°30<br />

400 210 145 268 191 268 191 1°30<br />

450 218 151 280 200 280 200 1°30<br />

500 271 180 364 257 364 257 1°30<br />

600 287 193 389 275 389 275 1°30<br />

700 391 268 1°<br />

750 402 277 1°<br />

800 411 283 1°<br />

900 400 276 1°<br />

1000 417 288 1°<br />

1200 445 308 1°<br />

1400 450 310 1°<br />

mark