Fig. 10.2.b.<br />
Support distance<br />
When using non locked rubber seal joints or mechanical couplers, pipelines must be anchored at each<br />
change in pipe direction, to prevent the pipes coming apart.Sideways movement is prevented by clamping.<br />
Where mechanical couplers are fitted, sideways movement can be avoided by scuring the coupler itself.<br />
Fig. 10.2.c. Fig. 10.2.d.<br />
LO<br />
Please note that rubber seal lock joints must be fully extended. This means that the locking strip is pinched<br />
between the stop in the socket and the stop in the spigot end. This prevents movement of pipe sections and overloading<br />
at bends and tees. Mechanical stretching is preferable; the results can be seen by inspection of the position of the<br />
locking strip through the insert hole. Extending can also be done by pressurizing the main line (0.8 x working pressure).<br />
Take care that the pipe sections are not pushed off their supports. In order to prevent this the lower part of the clip<br />
should be tightened temporarily and the upper part of the clip should be loosened. Relocate any moved pipe clips<br />
in their original position.After fully extending, the branch pipe sections can be installed.<br />
Wavistrong <strong>Installation</strong> <strong>Manual</strong><br />
47<br />
Max. 0,2 LO