9.5. Relief plates<br />
Where pipes are installed close to the surface or where weight of the soil exceeds the permitted wall stress level relief<br />
plates can be used. The relief plates may only be used if:<br />
A The ground consists of sand to a considerable depth.<br />
B The trench is to be filled with sand and very well compacted.<br />
These plates should have a rebate equal to the diameter of the pipe 5-10 cm deep. This rebate must be kept free from<br />
soil during installation for example by means of synthetic foam. The dimensions of the relief plate must be chosen so<br />
that the load-bearing capacity of the foundation is not exceeded. Select the correct size of the relief plate so that the<br />
load bearing capacity of the foundation is not exceeded. The distance between the relief plate and crown of the pipe<br />
may be maximum 0.5 x ID.<br />
Fig. 9.5.a.<br />
The plate must not be installed too high because the spread of the load will cause increased pressure on the pipe as in<br />
fig.9.5.b. Positioning the relief plate within the recommended distance, i.e. ≤ 0.5 x ID, provides better side support.<br />
Fig. 9.5.b.<br />
0,5 D<br />
45°<br />
top load<br />
free space<br />
D<br />
top load<br />
free space<br />
Wavistrong <strong>Installation</strong> <strong>Manual</strong><br />
41<br />
polystyrene foam<br />
relief plate<br />
relief plate<br />
spread<br />
relieving