a) Signals (4-20 mA or switch contact): 6/12 pair individually and over all shielded<br />

(screened) and armoured, twisted, 0.5 mm conductor.<br />

b) Thermocouple: 6/12 pair thermocouple extension cable (20 AWG)<br />

c) RTD: 8 Triad 1.5 mm˜ conductor.<br />

d) Solenoid valves (110 V DC): 6/12 Pair shielded, armoured, 1.5 mm˜ conductor.<br />

Higher conductor size shall be selected to limit the voltage drop within the specified<br />

limit.<br />

2.22.2 The colour of outer sheath, inner sheath and individual core <strong>for</strong> each type of cable shall<br />

be as mentioned below:<br />

Type of cable Signal type Outer sheath Conductor Insulation<br />

+ve -ve<br />

a) signalIS blue blue * Black *<br />

Non IS black blue * Black *<br />

b) control/power black red Black<br />

c) alarm IS, Non IS black white Black<br />

d) extension IS As per IEC 60584-3<br />

cable<br />

• Triad cable shall have blue, black and brown colour.<br />

2.23 Junction Boxes<br />

2.23.1 Junction boxes shall be used <strong>for</strong> interconnection in the field wherever necessary<br />

as per para 2.21.2. Analog signals (4 - 20 mA), switch contacts, temperature<br />

elements, LEL detectors, intrinsically safe, non intrinsically safe and low voltage<br />

contact signals shall be segregated in the separate junction boxes. Separate junction<br />

box shall also be used <strong>for</strong> signals and contacts connected to PLC, DCS or and other<br />

system.<br />

2.23.2 The junction box shall be suitable <strong>for</strong> the type of signal and type of multi core<br />

cables used as indicated in para 2.21.7. Unless otherwise specified, contractor must<br />

use the following type of junction boxes:<br />

For all intrinsically safe signals: Weatherproof junction boxes<br />

For all input/output connected: Explosion proof/flameproof<br />

to explosion proof/flameproof junction boxes instruments<br />

2.23.3 The junction boxes shall have cable entries suitable <strong>for</strong> the multi and single<br />

cables used. 20 % addition cable entries must be provided. Unused entries shall be<br />

plugged.<br />

2.23.4 The junction boxes shall have terminals suitable <strong>for</strong> the cable wire size and shall<br />

preferably be of Phoenix or equivalent make. All junction boxes used in intrinsically<br />

safe service shall be sky blue in colour while those in non-intrinsically safe service shall<br />

be painted gray.<br />

2.23.5 The multi cable entry <strong>for</strong> 6 pair Junction Box (JB) shall be 1" NPTF and <strong>for</strong> 12<br />

pair / 8 triad junction box, it shall be 1 1/2" NPTF. Each junction box shall be provided<br />

with 2 multi cable entries with one plugged with weatherproof, flameproof plug as<br />

required. Multi cable entries shall be from the bottom whereas 1 pair/triad from the<br />

STANDARD SPECIFICATION FOR<br />

SPECIFICATION REV-0<br />

<strong>GAIL</strong> (INDIA) LTD INSTRUMENTATION WORKS<br />

Page 17 of<br />

NEW DELHI<br />

S-08-02-004<br />

73<br />