specified area classification and weather proof to IP65/NEMA-4 and vendor shall<br />

supply necessary isolating barriers between the transducers and<br />

preamplifier/transmitter However the transducer/sensor housing can be flameproof<br />

(EEx d) certified suitable <strong>for</strong> the specified area classification instead of intrinsically<br />

safe.<br />

6.10 Overall pressure drops across the meter assembly including meter runs shall<br />

be less than 0.1 Kg/cm2g. Pressure drop calculation across the meter shall be<br />

furnished.<br />

6.12 Ultrasonic flow meter spool inside diameter to meet the specified I.D and<br />

internal surface roughness shall be as per <strong>standard</strong> AGA Report no. 9.<br />

7.0 METER ELECTRONICS AND SIGNAL PROCESSING<br />

7.1 Meter assembly shall include a signal processing unit to per<strong>for</strong>m all control of<br />

the transducers and per<strong>for</strong>m all calculations and statistical averaging <strong>for</strong> calculating<br />

flow rate.<br />

7.2 Extensive Diagnostic capability shall be provided to allow monitoring of<br />

operating parameters of the meter, health of the transducers and signal quality etc.<br />

These shall include parameters required to characterize the per<strong>for</strong>mance of the meter<br />

and confirm its compliance to AGA-9. The diagnostic functions shall be supported by a<br />

PC-based engineering/maintenance software tool.<br />

7.3 Signal processing unit shall per<strong>for</strong>m all flow computer functions, including<br />

calculations to correct <strong>for</strong> pressure, temperature and compressibility to provide<br />

corrected flow rates and flow totals at <strong>standard</strong> conditions. Compressibility<br />

calculations shall be based on the latest version of AGA Report No.8 using the<br />

detailed characterization method. Gas quality data, shall be input via the station PLC<br />

or RTU from live GC data from the nearest online gas chromatograph.<br />

7.4 The signal processing unit shall be equipped with a minimum of two serial<br />

communication ports. One port shall be used <strong>for</strong> connection to the station PLC / RTU<br />

or flow computer. The second port shall be used <strong>for</strong> maintenance and diagnostic<br />

support functions.<br />

7.5 The serial port communication channels shall each be configurable <strong>for</strong> speeds<br />

of 1200, 2400, 4800 or 9600 bits per second. The physical interface <strong>for</strong> each serial<br />

port shall support EIA-485 and EIA-232 <strong>standard</strong>s. Each port shall be equipped with<br />

optical protection to provide both galvanic isolation and surge suppression.<br />

7.6 The serial ports shall use MODBUS protocol as a MODBUS slave device. It shall<br />

support both RTU mode and ASCII mode communications. RTU mode shall be used<br />

<strong>for</strong> communicating with the SCADA/RTU/PLC or the flow computer.<br />

7.7 All operating parameters and flow data shall be accessible via the serial ports.<br />

Analog values retrieved via the serial communication port shall be scaled in<br />

engineering units. IEEE floating <strong>for</strong>mat shall be used. Status in<strong>for</strong>mation shall be<br />

available as either bit packed 16-bit MODBUS holding registers or as single bit<br />

MODBUS data. Operational data shall be user configurable to be in metric units or<br />

imperial units and shall include the following as a minimum:<br />

Uncorrected and corrected <strong>for</strong>ward direction flow rate<br />

Uncorrected and corrected reverse direction flow rate<br />

STANDARD SPECIFICATION FOR SPECIFICATION REV-0<br />

<strong>GAIL</strong> (INDIA) ULTRASONIC METERS<br />

Page 11<br />

S-08-02-022 of 17<br />