Impact of Drivetrain on Wind Farm VAR Control - Upwind
Impact of Drivetrain on Wind Farm VAR Control - Upwind
Impact of Drivetrain on Wind Farm VAR Control - Upwind
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
UPWIND<br />
SCR:20<br />
SCR:5<br />
y-axis (min) y-axis (max) y-axis (min) y-axis (max)<br />
SCR:3<br />
Figure 3-2. System resp<strong>on</strong>se to a step reactive power command (Qcmd) for different SCRs.<br />
3.2.2 Resp<strong>on</strong>se to a Step Change <str<strong>on</strong>g>of</str<strong>on</strong>g> Regulated Voltage<br />
The WTG resp<strong>on</strong>se to a step change <str<strong>on</strong>g>of</str<strong>on</strong>g> regulated voltage command at the POI was examined.<br />
Different wind farm power levels and different numbers <str<strong>on</strong>g>of</str<strong>on</strong>g> c<strong>on</strong>nected WTGs were investigated.<br />
The c<strong>on</strong>trol parameters listed in Table 3-1 were used.<br />
All WTGs are C<strong>on</strong>nected at Full Load (324 MW, Fn =1)<br />
Deliverable D5.9.1 21