Impact of Drivetrain on Wind Farm VAR Control - Upwind
Impact of Drivetrain on Wind Farm VAR Control - Upwind
Impact of Drivetrain on Wind Farm VAR Control - Upwind
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
UPWIND<br />
Scenario Case SCR MVA base<br />
WTG1 (MW)<br />
MVA base<br />
WTG2 (MW)<br />
Table 3-2. Summary results <str<strong>on</strong>g>of</str<strong>on</strong>g> c<strong>on</strong>sidered test cases for DFIG WTG<br />
<strong>Wind</strong> farm<br />
power (MW)<br />
Initial WTG1<br />
Q (M<strong>VAR</strong>)<br />
Initial WTG2<br />
Q (M<strong>VAR</strong>)<br />
Initial WTG1<br />
V (pu)<br />
Initial WTG2<br />
V (pu)<br />
Settling<br />
time (sec) *<br />
1 1 20 180 180 324 2.617 2.617 1.026 1.026 5.3<br />
1 2 5 180 180 324 2.617 2.617 1.026 1.026 5.7<br />
1 3 3 180 180 324 2.617 2.617 1.026 1.026 5<br />
2 4 20 180 180 324 -0.138 -0.137 1.025 1.018 999<br />
2 5 5 180 180 324 -0.137 -0.138 1.025 1.018 6.1<br />
2 6 3 180 180 324 -0.14 -0.14 1.025 1.018 5.7<br />
3 7 20 180 90 243 3.991 1.995 1.027 1.027 999<br />
3 8 5 180 90 243 3.991 1.995 1.027 1.027 8<br />
3 9 3 180 90 243 3.991 1.996 1.027 1.027 7.4<br />
4 10 20 360 N/A 324 5.261 0 1.026 0 5.4<br />
4 11 5 360 N/A 324 5.261 0 1.026 0 5.8<br />
4 12 3 360 N/A 324 5.26 0 1.026 0 5.1<br />
5 13 20 360 N/A 162 -3.743 0 1.017 0 999<br />
5 14 5 360 N/A 162 -3.743 0 1.017 0 6.4<br />
5 15 3 360 N/A 162 -3.743 0 1.017 0 6.4<br />
6 16 20 180 N/A 162 8.851 0 1.029 0 999 Fn=1<br />
6 17 5 180 N/A 162 8.851 0 1.029 0 12.2<br />
6 18 3 180 N/A 162 8.851 0 1.029 0 11.7<br />
7 19 20 180 N/A 162 8.851 0 1.029 0 999 Fn=0.5<br />
7 20 5 180 N/A 162 8.851 0 1.029 0 6.3<br />
7 21 3 180 N/A 162 8.851 0 1.029 0 6.2<br />
8 22 3 360 N/A 324 5.261 0 1.026 0 1.8 Settings <str<strong>on</strong>g>of</str<strong>on</strong>g> SCR 20<br />
were<br />
SCR 3<br />
applied to<br />
8 23 5 360 N/A 324 5.26 0 1.026 0 1.4 Settings <str<strong>on</strong>g>of</str<strong>on</strong>g> SCR 20<br />
were<br />
SCR 5<br />
applied to<br />
8 24 20 360 N/A 324 5.261 0 1.026 0 999 Settings <str<strong>on</strong>g>of</str<strong>on</strong>g> SCR 3<br />
were applied to<br />
9 25 20 360 N/A 162 41.945 0 1.043 0 6<br />
SCR 20<br />
Higher initial WTG<br />
terminal voltage<br />
*Settling time <str<strong>on</strong>g>of</str<strong>on</strong>g> 999 sec indicates inability <str<strong>on</strong>g>of</str<strong>on</strong>g> the POI voltage to recover back to the steady state value<br />
Deliverable D5.9.1 29<br />
Notes