Impact of Drivetrain on Wind Farm VAR Control - Upwind
Impact of Drivetrain on Wind Farm VAR Control - Upwind
Impact of Drivetrain on Wind Farm VAR Control - Upwind
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
UPWIND<br />
4.2.4 <strong>Wind</strong> <strong>Farm</strong> <strong>VAR</strong> C<strong>on</strong>trol with WTG Reactive Power C<strong>on</strong>trol Implementati<strong>on</strong><br />
The same block diagram used with static-type excitati<strong>on</strong> for <strong>VAR</strong> c<strong>on</strong>trol implementing the<br />
WTG reactive power c<strong>on</strong>trol was simulated with the brushless-type. The WTG reactive c<strong>on</strong>trol<br />
loop c<strong>on</strong>siders the reactive power capability <str<strong>on</strong>g>of</str<strong>on</strong>g> the WTG in terms <str<strong>on</strong>g>of</str<strong>on</strong>g> the reactive power limits.<br />
The c<strong>on</strong>troller parameters were determined following the same guidelines. The values <str<strong>on</strong>g>of</str<strong>on</strong>g> Tq and<br />
Tvar were set to 0.5 and 3 sec<strong>on</strong>ds respectively. The <strong>on</strong>ly difference is the time c<strong>on</strong>stant <str<strong>on</strong>g>of</str<strong>on</strong>g> each<br />
excitati<strong>on</strong> type, which affects the estimati<strong>on</strong> <str<strong>on</strong>g>of</str<strong>on</strong>g> the reactive power PI c<strong>on</strong>troller parameters listed<br />
in Table 4-11 c<strong>on</strong>sidering all WTGs <strong>on</strong>line. The values <str<strong>on</strong>g>of</str<strong>on</strong>g> Kqi and Kqp were tuned to have a<br />
reas<strong>on</strong>able resp<strong>on</strong>se in terms <str<strong>on</strong>g>of</str<strong>on</strong>g> the settling time (<str<strong>on</strong>g>of</str<strong>on</strong>g> the order <str<strong>on</strong>g>of</str<strong>on</strong>g> a few sec<strong>on</strong>ds) to a step change<br />
<str<strong>on</strong>g>of</str<strong>on</strong>g> 0.3 pu <str<strong>on</strong>g>of</str<strong>on</strong>g> the aggregate WTG reference reactive power (Qref) as shown in Figure 4-20. The<br />
WTG voltage limits were not applied to test the reactive power loop resp<strong>on</strong>se.<br />
Table 4-11. <strong>Wind</strong> farm <strong>VAR</strong> c<strong>on</strong>trol parameters with reactive power c<strong>on</strong>trol implementati<strong>on</strong> with<br />
brushless excitati<strong>on</strong> system<br />
SCR Tq<br />
Tvar<br />
Kqi Kqp Ki Kp<br />
(sec) (sec)<br />
20 0.5 3 0.5 0.45 6.66 3.33<br />
5 0.5 3 0.82 0.5 1.66 0.833<br />
3 0.5 3 1.08 0.45 1.0 0.5<br />
The resp<strong>on</strong>se to the same step change <str<strong>on</strong>g>of</str<strong>on</strong>g> the POI voltage applied with the static-type excitati<strong>on</strong><br />
was tested for the brushless-type. A reas<strong>on</strong>able time resp<strong>on</strong>se was obtained as shown in Figure<br />
4-21 with all WTGs in service and in Figure 4-22 with half <str<strong>on</strong>g>of</str<strong>on</strong>g> the WTGs in service.<br />
Deliverable D5.9.1 59