Impact of Drivetrain on Wind Farm VAR Control - Upwind
Impact of Drivetrain on Wind Farm VAR Control - Upwind
Impact of Drivetrain on Wind Farm VAR Control - Upwind
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
UPWIND<br />
Vreg_ref<br />
+<br />
-<br />
K K<br />
i p<br />
( 1+<br />
s)<br />
s K<br />
i<br />
VWTG_min<br />
VWTG_max<br />
VWTG_ref<br />
+<br />
-<br />
K K<br />
K +<br />
ie<br />
+<br />
de<br />
pe s 1+<br />
sT<br />
d<br />
ke<br />
1+<br />
sT<br />
Deliverable D5.9.1 55<br />
Emin<br />
Emax<br />
e<br />
VWTG<br />
X<br />
Efd<br />
Generator<br />
1 + s T ′<br />
do<br />
Figure 4-17. <strong>Wind</strong> farm <strong>VAR</strong> c<strong>on</strong>trol block diagram with brushless excitati<strong>on</strong> system.<br />
The selected PI c<strong>on</strong>trol parameters are listed in Table 4-9. Tvar was set to 3 sec<strong>on</strong>ds with system<br />
SCRs 3 and 5. It was set to 5 sec<strong>on</strong>ds with SCR 20 to avoid voltage collapse associated with the<br />
slower resp<strong>on</strong>se <str<strong>on</strong>g>of</str<strong>on</strong>g> the excitati<strong>on</strong> system when half <str<strong>on</strong>g>of</str<strong>on</strong>g> the WTGs are <strong>on</strong>line. The value <str<strong>on</strong>g>of</str<strong>on</strong>g> Kp/Ki<br />
was set to 2 for all cases, which is the estimated time c<strong>on</strong>stant <str<strong>on</strong>g>of</str<strong>on</strong>g> the excitati<strong>on</strong> system without<br />
the <strong>VAR</strong> c<strong>on</strong>trol implementati<strong>on</strong>.<br />
1<br />
VWTG<br />
Table 4-9. <strong>VAR</strong> c<strong>on</strong>trol parameters with brushless excitati<strong>on</strong> system<br />
SCR Tvar (sec) Fsc Ki Kp<br />
20 5 0.2 1 2<br />
5 3 0.49 0.67 1.35<br />
3 3 0.62 0.53 1.07<br />
As noted previously, adjusting Fsc with the variati<strong>on</strong> <str<strong>on</strong>g>of</str<strong>on</strong>g> the number <str<strong>on</strong>g>of</str<strong>on</strong>g> c<strong>on</strong>nected WTGs till 50%<br />
would not have a significant impact due to the small variati<strong>on</strong> <str<strong>on</strong>g>of</str<strong>on</strong>g> the Fsc value for the same<br />
system SCR. Figure 4-18 shows the system resp<strong>on</strong>se with SCR <str<strong>on</strong>g>of</str<strong>on</strong>g> 5 with half <str<strong>on</strong>g>of</str<strong>on</strong>g> the WTGs in<br />
service with and without adjusting Fsc. The figure c<strong>on</strong>firms the previous assumpti<strong>on</strong>s where<br />
there is no noticeable resp<strong>on</strong>se difference. Therefore, the c<strong>on</strong>trol settings listed in Table 4-9,<br />
which are determined with all WTGs in service, can be used as the default settings. However,<br />
with further lower porti<strong>on</strong> <str<strong>on</strong>g>of</str<strong>on</strong>g> c<strong>on</strong>nected WTGs, the settings should be adjusted.<br />
Fsc<br />
Vreg