APPENDIX 2.6<br />

ENGINE ROOM - RESTORE POWER AFTER ALTERNATORS TRIP OUT<br />

Following incident on 4/12/08, ship blacked out:<br />

Status: Breakers tripped out, alternators running, unable to close breakers, ship on<br />

emergency power:<br />

1. Open all circuit breakers on main switchboard.<br />

2. Close main breaker from alternator running.<br />

3. If breaker closes, voltage OK, close breakers for lights and steering.<br />

4. Lights and steering OK, check all distribution boards for burnt contactors etc. to<br />

locate fault. Start with larger electric motors, e.g. fridge compressors.<br />

5. Once fault found, isolate (tag out) faulty circuit and then close other breakers on<br />

main switchboard.<br />

NOTE<br />

1. If unable to find fault, close breakers systematically until alternator trips out. Last<br />

breaker closed is therefore faulty circuit.<br />

2. An external soft short across 2 phases of a large 415 V contactor may trip alternators<br />

off board without tripping the main circuit breaker for that particular circuit.<br />

3. When ship blacks out, Propeller goes to full pitch and Main Engine goes to full<br />

throttle. Undo bypass valves next to hand throttle and control engine with the hand<br />

throttle in Engine Room.<br />

Append 2.6 - Alternators Tripout.docx 1<br />

Revised: November 2010