3.2 Space Requirement for Yakut Elmas / Yakut Plus / Elmas Plus<br />
Distance between back surface of boiler and wall must be minimum 0.8 meter.<br />
63 9810.0156 – Rev.04 –12/01/2007<br />
ELMAS SERIE<br />
YAKUT SERIE<br />
Installation<br />
YAKUT PLUS<br />
SERIE<br />
YAKUT PLUS<br />
SERIE<br />
10 12 15 18 20 22 25 28 30 35 40 50 55 60 70 80 100 125 160 200 250<br />
X mm 600 600 600 600 750 750 750 750 750 750 1000 1000 1000 1000 1000 1000 1000 1200 1200 1400 1500<br />
Y mm 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 2000 2000 2000 2000 2000 2000 2200 2300 2300 2500 3000<br />
*) 0.5 meter distance is necessary from the<br />
sides for assembling of side casing.<br />
Besides, if the boiler is settled after assembling of<br />
side casing, this distance may be reduced.<br />
If settlement of boiler is done as burner opens<br />
towards wall, distance between boiler and wall depends on<br />
the burner dimension. Burner cover must be openable at<br />
least 90° to provide the easy cleaning of the boiler and<br />
easy removing process of turbulators.<br />