BOILER<br />

TYPE<br />

3.2 Space Requirement for Yakut Elmas / Yakut Plus / Elmas Plus<br />

Distance between back surface of boiler and wall must be minimum 0.8 meter.<br />

63 9810.0156 – Rev.04 –12/01/2007<br />

ELMAS SERIE<br />

YAKUT SERIE<br />

Installation<br />

YAKUT PLUS<br />

SERIE<br />

YAKUT PLUS<br />

SERIE<br />

10 12 15 18 20 22 25 28 30 35 40 50 55 60 70 80 100 125 160 200 250<br />

X mm 600 600 600 600 750 750 750 750 750 750 1000 1000 1000 1000 1000 1000 1000 1200 1200 1400 1500<br />

Y mm 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 2000 2000 2000 2000 2000 2000 2200 2300 2300 2500 3000<br />

*) 0.5 meter distance is necessary from the<br />

sides for assembling of side casing.<br />

Besides, if the boiler is settled after assembling of<br />

side casing, this distance may be reduced.<br />

If settlement of boiler is done as burner opens<br />

towards wall, distance between boiler and wall depends on<br />

the burner dimension. Burner cover must be openable at<br />

least 90° to provide the easy cleaning of the boiler and<br />

easy removing process of turbulators.<br />

If burner is opened towards right side, hinge metal bars<br />

of the boiler cover must be installed to right side.<br />

13