Operating/First Start Up<br />

6.3 Emergency Operation<br />

63 9810.0156 – Rev.04 –12/01/2007<br />

When the pressure goes under 0,5 bar or goes<br />

up 1,5 times over opening limit of relief valve (4,5 bar),<br />

boiler must be shut down by applying emergency<br />

operation immediately. Ensure that burner is shut<br />

down and leave boiler for getting cold by itself.<br />

Do not load water to boiler absolutely, open the<br />

door of boiler room and get away from boiler. Call<br />

authorized service immediately.<br />

IMPORTANT WARNING !<br />

Do not load cold water to boiler in any condition.<br />

This situation may cause to important damages and<br />

vital dangers.<br />

Electricshock Danger! Before protective hat and<br />

pieces of cover is taken out, all electrical connections on<br />

boiler must be disassembled. Works that will be done when<br />

electric is on, must be carried on by authorized people after<br />

all necessary precuations are supplied.<br />

As boiler works, in case of circumstances such as<br />

limit exceeding of temperature or/and pressure,<br />

overworking, steam overloading etc., boiler thermostat<br />

must be shut down, pump must go on circulating certainly,<br />

all gas and fuel valves must be shut down, boiler must be<br />

left to get cold by itself. Uncapable and unlicenced people<br />

must not barge to boiler. Opposite conditions may cause<br />

serious life and property losses. The boiler will be out of<br />

warranty in these conditions.<br />