Page 6<br />

<strong>Australian</strong> <strong>Building</strong> <strong>Codes</strong> <strong>Board</strong><br />

(d)<br />

Deemed-to-Satisfy Provisions<br />

door serving as, or forming part of, a requiredexit in a storeyrequired to be provided<br />

with emergency lighting in accordance with E4.2.<br />

E4.6 Direction signs<br />

NSW E4.6<br />

If an exit is not readily apparent to persons occupying or visiting the building then exit<br />

signs must be installed in appropriate positions in corridors, hallways, lobbies, and the<br />

like, indicating the direction to a requiredexit.<br />

E4.7 Class 2 and 3 buildings and Class 4 parts: Exemptions<br />

E4.5 does not apply to—<br />

(a)<br />

(b)<br />

a Class 2 building in which every door referred to is clearly and legibly labelled on<br />

the side remote from the exit or balcony—<br />

(i)<br />

(ii)<br />

with the word “EXIT” in capital letters 25 mm high in a colour contrasting with<br />

that of the background; or<br />

by some other suitable method; and<br />

an entrance door of a sole-occupancy unit in a Class 2 or 3 building or Class 4 part<br />

of a building.<br />

E4.8 Design and operation of exit signs<br />

Every required exit sign must comply with—<br />

(a)<br />

(b)<br />

comply with AS 2293.1; andor<br />

for a photoluminescent exit sign, Specification E4.8; and<br />

be clearly visible at all times when the building is occupied by any person having<br />

the right of legal entry to the building.<br />

be clearly visible at all times when the building is occupied by any person having the right<br />

of legal entry to the building.<br />

E4.9 Sound systems and intercom systems for emergency<br />

purposes<br />

A sound system and intercom system for emergency purposes complying where<br />

applicable with AS 1670.4 must be installed—<br />

(a)<br />

(b)<br />

(c)<br />

in a building with an effective height of more than 25 m; and<br />

in a Class 3 building having a rise in storeys of more than 2 and used as—<br />

(i)<br />

(ii)<br />

the residential part of a school; or<br />

accommodation for the aged, children or people with a disability; and<br />

in a Class 3 building used as a residential aged care building, except that the<br />

system—<br />

(i)<br />

PUBLIC COMMENT DRAFT<br />

must be arranged to provide a warning for occupants; and<br />

E4.6<br />