Page 18<br />
<strong>Australian</strong> <strong>Building</strong> <strong>Codes</strong> <strong>Board</strong><br />
Deemed-to-Satisfy Provisions<br />
G P/H Orientation Sector (refer Figure J2.3)<br />
(refer Figure (refer Figure North North East South South South West North<br />
J2.4) J2.4) east east west west<br />
0.0 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00<br />
0.2 0.97 0.98 0.98 0.98 0.97 0.98 0.98 0.97<br />
0.4 0.88 0.93 0.94 0.93 0.93 0.93 0.93 0.92<br />
0.6 0.78 0.84 0.87 0.86 0.87 0.86 0.87 0.83<br />
More than 0.8 0.66 0.74 0.79 0.79 0.81 0.80 0.80 0.74<br />
500 mm but<br />
not more than<br />
1.0 0.56 0.64 0.71 0.72 0.75 0.73 0.73 0.64<br />
1200 mm 1.2 0.49 0.56 0.65 0.66 0.71 0.68 0.66 0.57<br />
1.4 0.46 0.50 0.59 0.61 0.68 0.64 0.61 0.51<br />
1.6 0.44 0.45 0.54 0.57 0.66 0.60 0.56 0.47<br />
1.8 0.43 0.42 0.49 0.54 0.63 0.57 0.52 0.44<br />
2.0 0.42 0.40 0.46 0.52 0.61 0.53 0.49 0.42<br />
0.0 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00<br />
0.2 0.98 0.99 0.99 0.99 0.99 0.99 0.99 0.99<br />
0.4 0.93 0.96 0.96 0.96 0.95 0.96 0.96 0.95<br />
0.6 0.86 0.91 0.93 0.91 0.91 0.91 0.92 0.90<br />
More than 0.8 0.78 0.84 0.87 0.86 0.87 0.86 0.87 0.83<br />
1200 mm but<br />
less than<br />
1.0 0.69 0.77 0.82 0.80 0.82 0.81 0.81 0.76<br />
1800 mm 1.2 0.60 0.69 0.75 0.75 0.78 0.76 0.76 0.68<br />
Notes:<br />
1.4 0.54 0.62 0.69 0.70 0.74 0.72 0.70 0.62<br />
1.6 0.49 0.55 0.65 0.65 0.71 0.68 0.66 0.56<br />
1.8 0.47 0.50 0.60 0.62 0.69 0.64 0.61 0.52<br />
2.0 0.45 0.46 0.55 0.58 0.67 0.61 0.57 0.48<br />
1. Where G is 1800 mm or more, the cooling shading multiplier is to be taken as 1.0.<br />
2. The cooling shading multiplier for P/H values between those shown in Table J2.4d can be<br />
interpolated.<br />
3. For glazing in the internal fabric use the appropriate value for the south orientation sector<br />
with a P/H value of 2.0.<br />
PUBLIC COMMENT DRAFT<br />
Table J2.4e SHADING MULTIPLIERS FOR GLAZING IN THE INTERNAL FABRIC<br />
Climate zone<br />
Shading multiplier<br />
Heating (S H ) Cooling (S C )<br />
1, 2 and 3 1.0 0.49<br />
4 and 5 0.64 0.54<br />
J2.4<br />
NCC2014 Volume One