Altivar 38 - variable speed drive - user's manual
Altivar 38 - variable speed drive - user's manual
Altivar 38 - variable speed drive - user's manual
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Mounting in a Wall-fixing or Floor-standing<br />
Enclosure<br />
Observe the mounting recommendations on the previous page.<br />
To ensure proper air circulation in the <strong>drive</strong>:<br />
- Fit ventilation grilles<br />
- Ensure that ventilation is adequate: if not, install<br />
forced ventilation with a filter<br />
- Use special IP 54 filters<br />
Dust and damp proof metal wall-fixing or floor-standing<br />
enclosure (IP 54 degree of protection)<br />
The <strong>drive</strong> must be mounted in a dust and damp proof casing in certain environmental conditions: dust,<br />
corrosive gases, high humidity with risk of condensation and dripping water, splashing liquid, etc.<br />
ENGLISH<br />
To avoid hot spots in the <strong>drive</strong>, add a fan to circulate the air inside the enclosure, reference VW3A5882• (see<br />
ATV<strong>38</strong> catalogue).<br />
This enables the <strong>drive</strong> to be used in an enclosure where the maximum internal temperature can reach 60 °C.<br />
Calculating the size of the enclosure<br />
Maximum thermal resistance Rth (°C/W) :<br />
Rth =<br />
θ° - θ°e<br />
P<br />
θ° = maximum temperature inside enclosure in °C<br />
θ°e = maximum external temperature in °C<br />
P = total power dissipated in the enclosure in W<br />
Power dissipated by the <strong>drive</strong>: see section Selecting a <strong>drive</strong>.<br />
Add the power dissipated by the other equipment components.<br />
Useful heat dissipation surface of enclosure S (m 2 ):<br />
(sides + top + front panel if wall-mounted)<br />
S =<br />
K<br />
Rth<br />
K = enclosure thermal resistance per m 2<br />
For metal enclosure:<br />
K = 0.12 with internal fan<br />
K = 0.15 without fan<br />
Caution: Do not use insulated enclosures, as they have a poor level of conductivity.<br />
78