Technical Specifications<br />

Electrical characteristics<br />

ENGLISH<br />

Power Voltage • <strong>38</strong>0 V - 10% to 460 V + 10% 3-phase<br />

supply<br />

Frequency • 50/60 Hz ± 5%<br />

Output voltage<br />

Maximum voltage equal to line supply voltage<br />

Electrical isolation<br />

Electrical isolation between power and control (inputs, outputs, power<br />

supplies)<br />

Output frequency range 0.1 to 500 Hz<br />

Switching frequency Configurable:<br />

• without derating:<br />

0.5 - 1 - 2 - 4 kHz for ATV<strong>38</strong>HU18N4 to D46N4(X) <strong>drive</strong>s<br />

0.5 - 1 - 2 kHz for ATV<strong>38</strong>HD54N4(X) to C33N4X <strong>drive</strong>s<br />

• without derating with intermittent operating cycle<br />

or with derating by one power rating in continuous operation:<br />

8 - 12 - 16 kHz for ATV<strong>38</strong>HU18N4 to D23N4 <strong>drive</strong>s<br />

8 - 12 kHz for ATV<strong>38</strong>HD25N4(X) to D46N4(X) <strong>drive</strong>s<br />

4 - 8 kHz for ATV<strong>38</strong>HD54N4(X) to D79N4(X) <strong>drive</strong>s<br />

4 kHz for ATV<strong>38</strong>HC10N4X to C33N4X <strong>drive</strong>s<br />

Speed range 1 to 10<br />

Braking torque<br />

30% of nominal motor torque without braking resistor (typical value) for low<br />

power ratings<br />

Transient overtorque 110% of nominal motor torque (typical values to ±10%) for 60 seconds<br />

Protection and safety<br />

features of <strong>drive</strong><br />

• Short-circuit protection:<br />

- between output phases<br />

- between output phases and earth<br />

- on internal supply outputs<br />

• Thermal protection against overheating and overcurrents<br />

• Supply undervoltage and overvoltage safety circuits<br />

• Loss of input phase safety circuit (avoids single-phase operation, on all 3-<br />

phase <strong>drive</strong>s)<br />

Motor protection • Thermal protection integrated in <strong>drive</strong> via continuous calculation of I 2 t<br />

taking <strong>speed</strong> into account<br />

Motor thermal state saved when the <strong>drive</strong> is switched off. This function can<br />

be modified (via the operator terminal or programming terminal or via the<br />

PC software), depending on the type of motor cooling<br />

• Protection against motor phase breaks<br />

• Protection via PTC probes with option card<br />