Electromagnetic Compatibility - Wiring<br />
<strong>Altivar</strong> <strong>38</strong> without integral EMC filter ATV<strong>38</strong>HC10N4X to<br />
HC33N4X<br />
Line chokes are compulsory if the line supply prospective short-circuit current is less than 22 kA. These chokes<br />
can be used to provide improved protection against overvoltages on the line supply and to reduce harmonic<br />
distortion of the current produced by the <strong>drive</strong>. The chokes are used to limit the line current.<br />
ENGLISH<br />
Principle<br />
• Grounds between <strong>drive</strong>, motor and cable shielding must have "high frequency" equipotentiality.<br />
• Use shielded cables with shielding connected to the ground at both ends of the motor cable, and controlsignalling<br />
cables. Conduit or metal ducting can be used for part of the shielding length provided that there<br />
is no break in continuity.<br />
• Ensure maximum separation between the power supply cable (line supply) and the motor cable.<br />
Power wiring<br />
The power wiring should consist of cables with 4 conductors or individual cables maintained as close as<br />
possible to the PE cable. Take care to route the motor cables well away from the power supply cables.<br />
The power supply cables are not shielded. If a radio interference filter is used, the grounds for the filter and the<br />
<strong>drive</strong> should be at the same potential with low-impedance links at high frequency (fixed to unpainted metal<br />
plate with anti-corrosion treatment/machine ground wiring). The filter should be fitted as close as possible to<br />
the <strong>drive</strong>.<br />
If the environment is sensitive to radiated radio interference, the motor cables should be shielded. On the <strong>drive</strong><br />
side, fix and connect the shielding to the machine ground with rustproof clamps. The main function of the motor<br />
cable shielding is to limit their radio frequency radiation. Therefore, use 4-pole cables for the motor, connecting<br />
each end of the shielding in accordance with established practice for High Frequency wiring. The type of<br />
protective material (copper or steel) is less important than the quality of the connection at both ends. An<br />
alternative is to use a metal cable duct with good conductivity and no break in continuity.<br />
Note: when using a cable with a protective sleeve (NYCY type) which fulfils the dual function of PE + screen,<br />
it must be connected correctly to both the <strong>drive</strong> and the motor (its radiation efficiency is reduced).<br />
Control wiring<br />
Shielding clamp<br />
Cable grip. Check that the cable follows the path indicated<br />
by the clips<br />