Configurable I/O Application Functions<br />
PI error (code OPE): the image of the PI regulator error as a % of the sensor range (maximum feedback<br />
- minimum feedback).<br />
• AOL corresponds to the maximum error < 0.<br />
• AOH corresponds to the maximum error > 0.<br />
• AOH + AOL corresponds to a zero error (OPE = 0).<br />
2<br />
PI integral (code OPI): the image of the PI regulator error integral.<br />
• AOL corresponds to a zero integral.<br />
• AOH corresponds to a saturated integral.<br />
Motor power (code OPR): the image of the motor power consumption.<br />
• AOL corresponds to 0% of the nominal motor power.<br />
• AOH corresponds to 200% of the nominal motor power.<br />
Motor thermal state (code THR): the image of the motor thermal state, calculated.<br />
• AOL corresponds to 0%.<br />
• AOH corresponds to 200%.<br />
Drive thermal state (code THD): the image of the <strong>drive</strong> thermal state, calculated.<br />
• AOL corresponds to 0%.<br />
• AOH corresponds to 200%.<br />