Connection Diagrams<br />
3-phase power supply<br />
ÐQ1<br />
ENGLISH<br />
(2)<br />
(3)<br />
L1<br />
L2<br />
L3<br />
U<br />
V<br />
W<br />
R1A<br />
AO1<br />
R1C<br />
COM<br />
AI1<br />
+10<br />
AI2<br />
2<br />
4<br />
6<br />
1<br />
3<br />
5<br />
Without<br />
line<br />
contactor<br />
or<br />
With<br />
line<br />
contactor<br />
1 ÐQ22 ÐT1 1 ÐQ32<br />
ÐS2<br />
3 4 ÐQ2 5 6<br />
ÐS1<br />
Ð KM1<br />
A1 A2<br />
Ð KM1<br />
1<br />
3<br />
5<br />
A1<br />
Ð KM1<br />
R1A R1C 13 14<br />
(1)<br />
(4)<br />
A1<br />
2<br />
R1B<br />
4<br />
6<br />
LI1<br />
LI2<br />
LI3<br />
LI4<br />
+24<br />
R2A<br />
R2C<br />
U1<br />
V1<br />
W1<br />
M<br />
3 c<br />
X-YmA<br />
Motorfrequency<br />
Reference potentiometer<br />
X-YmA<br />
(1) ATV<strong>38</strong>HC10N4X to C33N4X: Line choke compulsory.<br />
ATV<strong>38</strong>HU18N4 to D23N4: Line choke if necessary.<br />
(2) Fault relay contacts for remote signalling of <strong>drive</strong> status.<br />
(3) Internal + 24 V. If an external + 24 V supply is used, connect the 0 V from that source to the COM terminal,<br />
do not use the + 24 terminal on the <strong>drive</strong>, and connect the common of the LI inputs to the + 24 V of the<br />
external supply.<br />
(4) R2 reassignable relay.<br />
Note:<br />
Fit interference suppressors to all inductive circuits near the <strong>drive</strong> or connected in the same circuit, such as<br />
relays, contactors, solenoid valves, fluorescent lighting, etc.<br />
Components which can be used in association with the <strong>Altivar</strong>: see catalogue.<br />