I/O Menu<br />
This menu can be accessed when the switch is in position .<br />
The assignments can only be modified in stop mode with the <strong>drive</strong> locked.<br />
Code<br />
Function<br />
LI2 LI2 Assign.<br />
See the summary table and description of the functions.<br />
The inputs and outputs available in the menu depend on the I/O cards installed (if any) in the <strong>drive</strong>, as well as<br />
the selections made previously in the control menu.<br />
Summary table of the logic input assignments (exc. 2-wire / 3-wire option)<br />
I/O extension option cards<br />
2 logic inputs LI5-LI6<br />
Drive without option<br />
3 logic inputs LI2 to LI4<br />
NO :Not assigned (Not assigned) X<br />
RV :Reverse (Reverse) X<br />
RP2:Switch ramp2 (Ramp switching) X<br />
JOG (Jog operation) X<br />
+SP: + Speed (+ <strong>speed</strong>) X<br />
-SP: - Speed (- <strong>speed</strong>) X<br />
PS2: 2 Preset Speeds (2 preset <strong>speed</strong>s) X<br />
PS4 : 4 Preset Speeds (4 preset <strong>speed</strong>s) X<br />
PS8 : 8 Preset Speeds (8 preset <strong>speed</strong>s) X<br />
NST:Freewhl Stop (Freewheel stop) X<br />
DCI:DC inject. (Injection stop) X<br />
FST:Fast stop (Fast stop) X<br />
CHP:Multi. Motor (Motor switching) X<br />
FLO:Forced Local (Forced local mode) X<br />
RST:Fault Reset (Fault reset) X<br />
RFC:Auto/Manu (Reference switching) X<br />
ATN:Auto Tuning (Auto-tuning) X<br />
PAU:PI Auto/Man (PI Auto/Man) If one AI = PIF X<br />
PR2:PI 2 Preset (2 preset PI references) If one AI = PIF X<br />
PR4:PI 4 Preset (4 preset PI references) If one AI = PIF X<br />
EDD:Ext flt. (external fault) X<br />
FTK: Forc.Keyp. (Force to keypad) X<br />
ENGLISH<br />
CAUTION: If a logic input is assigned to "Freewheel stop" or "Fast stop", start-up can only be<br />
performed by linking this input to the +24V, as these stop functions are active when the inputs are at<br />
state 0.<br />
102