Monitoring master unit<br />
- 46 -<br />
4.1 IP monitoring units – 5500.824, 5510.824<br />
Compact devices with dimensions 440×44×110, net weight 2 kg.<br />
It is possible to connect up to 8 analog, 20 digital sensors or 2 1-Wire readers, 16 dry contacts,<br />
up to 4 relay devices and up to 30 extension units, such as RS, BU or WT.<br />
Pic. 4.1:IP monitoring unit 5500.824/5510.824, front view<br />
Pic. 4.2: IP monitoring unit 5500.824/5510.824, front view<br />
Description of I/O on the front panel of 5500.824/ 5510.824<br />
Antenna is used by the GSM module of the system.<br />
SIM is needed for operation of GSM modem<br />
Micro SD provides the possibility to send voice messages.<br />
USB-port is used to connect USB flash drive or USB Cam.<br />
LAN-port for 10/100 Mbit, Ethernet connection using UTP/FTP cable.<br />
RS-485 port for connection of up to 30 extension units using UTP/FTP cable.<br />
TR switch is a load switch used to terminate extension devices for a long distance ~ 1km.<br />
Reset button. Hidden switch used for immediate system restart.<br />
LEDs on the front panel of 5500.824/ 5510.824<br />
PWR – Lights up several seconds after submission of power supply on the device.<br />
ALRM – Flashes when a disturbing event occurs in one of the sensors.<br />
PRG – Temporarily lights up during reprogramming of the device through USB port.<br />
ACT – Indicates exchange of data with extension units on RS-485 Bus.<br />
1, 2, 3, 4 – Shows state of relays on/off.<br />