- 50 -<br />

ACT – Indicates exchange of data with extension units on RS485 Bus.<br />

1, 2, 3, 4 – Shows state of outlets on/off.<br />

Pic 4.9: IP PDU 5510.008/5510.108 LEDs on the front side<br />

Description of I/O on the IP PDU back panel of 5510.008/ 5510.108<br />

The back panel of IP PDU contains the following I/O and LEDs (See Pic. 5.10):<br />

PWR 1, 2 connectors C14. Power cable 230V IEC60320 C13. There are built-in 10A<br />

fuses on each line.<br />

Outputs 1...8 connectors C13 230V with relay contacts. Max. load current per one outlet<br />

- 5A. Max. total load current - 20А. Cables used IEC60320 C14/С13. If needed power<br />

can be switched on/off on each outlet remotely via IP.<br />

Current of each outlet is measured and is shown in the interface. In addition, power consumption<br />

is shown.<br />

Possibility to use 3-level access to IP PDU, allowing certain user to control certain outlet.<br />

Pic. 4.10: IP PDUs 5510.008/5510.108, back view<br />

Pic. 4.11: IP PDUs 5510.008/5510.108, back view<br />