18 1 Step Modulation – Regulates the burner output in 6 steps in one-minute intervals. This reduces short cycling.<br />
1 = on, 0 = off<br />
o Indirect heater set point (flow)<br />
19 180<br />
Temperature default = 119 o to 180 o<br />
20 1 Not applicable<br />
NOTE: The maximum water temperature leaving the heater is limited to 185 o F.<br />
Table 11 - *Central <strong>Heat</strong>ing Curve Function<br />
Central heating demand is detected when the room thermostat closes. When an outside sensor is also connected, the supply<br />
temperature will depend on the factory default central heating curve.<br />
To set your heat curve, you will have to set the following parameters:<br />
1. Minimum outside design temperature: Function 8.<br />
Table 12 – Central <strong>Heat</strong>ing Curve – Factory Default<br />
2. Design supply water temperature at the minimum design outside temperature: Function 9.<br />
3. Maximum outside design temperature: Function 10.<br />
4. Design supply water temperature at the maximum outside temperature: Function 11.<br />
NOTE: The homeowner can adjust the heat curve down by adjusting the central heating temperature to a lower setting.<br />
LP-171 Rev. 10.2.13