INSPECTION ACTIVITIES<br />

DATE LAST COMPLETED<br />

PIPING 1 st YEAR 2 nd YEAR 3 rd YEAR 4 th YEAR*<br />

Near heater piping Check heater and system piping for any sign of leakage, make<br />

sure they are properly supported.<br />

Vent<br />

Check condition of all vent pipes and joints.<br />

<strong>Gas</strong><br />

Check <strong>Gas</strong> piping, test for leaks and signs of aging. Make sure<br />

all pipes are properly supported.<br />

SYSTEM<br />

Visual<br />

Do a full visual inspection of all system components.<br />

Functional<br />

Test all functions of the system (<strong>Heat</strong>, Safeties)<br />

Temperatures<br />

Verify safe settings on heater or Anti-Scald Valve<br />

Temperatures<br />

Verify programmed temperature settings<br />

ELECTRICAL<br />

Connections<br />

Check wire connections. Make sure they are tight.<br />

Smoke and CO<br />

detector<br />

Verify devices are installed and working properly. Change<br />

batteries if necessary.<br />

Circuit Breakers Check to see that the circuit breaker is clearly labeled. Exercise<br />

circuit breaker.<br />

CHAMBER/BURNER<br />

Combustion Chamber<br />

Spark Electrode<br />

Flame Probe<br />

CONDENSATE<br />

Neutralizer<br />

Condensate hose<br />

GAS<br />

Pressure<br />

Pressure Drop<br />

Check gas pipe for<br />

leaks<br />

COMBUSTION<br />

CO/CO2 Levels<br />

SAFETIES<br />

ECO (Energy Cut Off)<br />

Water Pressure Switch<br />

Thermistors<br />

FINAL INSPECTION<br />

Check list<br />

Check burner tube and combustion chamber coils. Clean<br />

according to maintenance section of manual. Vacuum<br />

combustion chamber.<br />

Clean. Set gap at ¼”.<br />

Clean. Check ionization in uA (d7 on status menu in Start-up<br />

Procedures). Record high fire and low fire.<br />

Check condensate neutralizer. Replace if necessary.<br />

Disconnect condensate hose. Clean out dirt. Fill with water to<br />

level of outlet and re-install. (NOTE: Verify the flow of<br />

condensate, making sure that the hose is properly connected<br />

during final inspection.)<br />

Measure incoming gas pressure (3.5” to 14” W.C.)<br />

Measure drop in pressure on light off (no more than 1” W.C.)<br />

Check piping for leaks. Verify that all are properly supported.<br />

Check CO and CO2 levels in Exhaust (See Start-up Procedures<br />

for ranges). Record at high and low fire.<br />

Check continuity on Flue and Water ECO. Replace if corroded.<br />

Check operation and for signs of leakage. Replace if corroded.<br />

Check wiring. Verify through ohms reading.<br />

Verify that you have completed entire check list. WARNING:<br />

FAILURE TO DO SO COULD RESULT IN SERIOUS INJURY<br />

OR DEATH.<br />

Review what you have done with the homeowner.<br />

Homeowner<br />

Table 19 - *Continue annual maintenance beyond the 4 th year as required.<br />

LP-171 Rev. 10.2.13