[Downloaded from Internet]<br />

• On-board Memory to store data during failure of GPRS network.<br />

• The EMCS Unit should have LCD Display and keypad. LED indications for the status<br />

of GSM Connectivity.<br />

• The EMCS device should have provision for interfacing with any ultrasonic level<br />

sensor and automatic valves so that complete automation is possible if required in future.<br />

• EMCS shall have ADC (Analog to Digital Converter) for sensor integration with<br />

following industry standard<br />

a. PT-100 Inputs – 2 Nos.<br />

b. 0-10 V Inputs – 2 Nos.<br />

c. 0/4-20mA Inputs – 4 Nos<br />

d. Digital Inputs - 2 Nos.<br />

Input Voltage 0-4 V as logic '0', 4 - 30V as logic '1'<br />

e. High Speed Inputs - 2 Nos.<br />

Input Voltage 0-3.5 V as logic „0, 3.5 - 30V as logic '1'<br />

f. Digital Outputs - 2 Nos.<br />

Potential Free Outputs (1 Common and 1 NO contacts)<br />

g. Maximum Input frequency 1 KHz<br />

h. Field Power Supply to Sensors<br />

i. DC 12 V Output - Range 11.5 to 13.8 VDC<br />

ii. DC 24 V Output - Range 21 to 26 VDC<br />

3. 2 Specification for Energy Meters – 3 Phase CT operated LT meter<br />

• 4 quadrant, bi-directional 3phase- 4 Wire Metering system<br />

• Accuracy Class 0.5S<br />

• CT Rating 5A, 3 CTs for measurement of Phase currents.<br />

• Display for viewing Parameters and Settings, Keypad for Setting of CT Ratio.<br />

• Communication interface shall be Modbus RTU on RS-485 network (2 Wire Halfduplex).<br />

[ Tenderer ] [ Page 34of 44 ] [For Sr.DEE/ADI ]