Cable route markers shall be provided along straight runs of the cables at the locations<br />
approved by <strong>Railway</strong>.<br />
Route markers shall be made out as per sketch with information as size, cores and<br />
grade of cable shall be displayed. Cable route indicators with IR engraved on it to be<br />
provided at every 50 meters.<br />
Jointing:<br />
Before jointing is commenced all safety precautions like isolation, discharging, earthing<br />
etc. shall be taken to ensure that the cable would not be in-advertantly charged from live<br />
supply. Metallic armour and external metallic bonding shall be connected to earth.<br />
Where cable is to be jointed with the existing cable the sequence should be so arranged,<br />
as to avoid crossing of cores while jointing.<br />
Note: For item no. 6 of SCHEDULE, digging and laying of cable to be done in garden<br />
area where trench should be taken 1 feet deep and filling back without bricks. Contractor<br />
shall have to repair plaster or bricks work if damaged<br />
(J) Technical specification for item No. 12 of SCHEDULE of rates and quantities:<br />
[Laying of cable in Air, Wall, Pipe etc]<br />
Cable shall be laid between poles and main boards. These cables are to be laid on wall /<br />
Pole / Air with suitable of clamps.<br />
Route of the cable.<br />
Before laying is under taken the route shall be marked in consultation with <strong>Railway</strong>'s<br />
representative at site.<br />
Jointing:<br />
Before jointing is commenced all safety precautions like isolation, discharging, earthing<br />
etc. shall be taken to ensure that the cable would not be in-advertantly charged from live<br />
supply. Where cable is to be jointed with the existing cable the sequence should be so<br />
arranged, as to avoid crossing of cores while jointing.<br />
The installation of cable including joints shall be carried out in accordance with code of<br />
practice as specified in relevant ISS as amended latest.<br />
(K) Technical specification for item no.13 of SCHEDULE of rate and quantities :<br />
[ Laying of cable in RCC area]<br />
The Contractor shall have to do laying of the existing cables in trench in the size of<br />
300mmx200 mm and laying of existing cable in same trench & resurfacing as earlier.<br />
The Digging of the trench should be carried out by excavation method in<br />
PCC/Road/Platform area.<br />
Contractor shall have to made trench by excavation method in pukka<br />
(PCC/Road/Platform) area. Digging of trench and it’s covering with PCC to be done by<br />
contractor. Filling of this trench shall be done with PCC having ratio of cement<br />
concrete and sand as per 1:2:4 ratio. Work shall be carrying out as per instruction of<br />
site in charge.<br />