• Alarm Function (refer to Figure 18)<br />

Figure 18 Alarm function<br />

Option<br />

Low alarm<br />

High alarm<br />

Low<br />

deadband<br />

High<br />

deadband<br />

Off delay<br />

On delay<br />

Description<br />

Sets the value where the relay will turn on in response to<br />

decreasing measured value. For example, if the low alarm is<br />

set for 1.0 and the measured value drops to 0.9, the relay<br />

activates.<br />

Sets the value where the relay will turn on in response to<br />

increasing measured value. For example, if the high alarm is<br />

set for 1.0 and the measured value increases to 1.1, the<br />

relay activates.<br />

Sets the range where the relay remains on after the<br />

measured value increases above the low alarm value. For<br />

example, if the low alarm is set for 1.0 and the low<br />

deadband is set for 0.5, the relay remains on between<br />

1.0 and 1.5. Default is 5% of the range.<br />

Sets the range where the relay remains on after the<br />

measured value decreases below the high alarm value. For<br />

example, if the high alarm is set for 4.0 and the high<br />

deadband is set for 0.5, the relay remains on between<br />

3.5 and 4.0. Default is 5% of the range.<br />

Sets a time (0-300 seconds) to delay the relay from normally<br />

turning off (Default: 0 seconds).<br />

Sets a delay time for the relay to turn on (Default:<br />

0 seconds).<br />

1 High alarm 5 ON delay<br />

2 High deadband 6 OFF delay<br />

3 Low deadband 7 Time (x-axis)<br />

4 Low alarm 8 Source (y-axis)<br />