• Feeder Control Function (refer to Figure 19 and Figure 20)<br />

Figure 19 Feeder control function<br />

Option<br />

Phase<br />

Set setpoint<br />

Deadband<br />

Overfeed timer<br />

Off delay<br />

On delay<br />

Description<br />

Defines the relay status if the process value exceeds the<br />

setpoint.<br />

High (default)—turns the relay on when the process value<br />

exceeds the setpoint.<br />

Low—turns the relay on when the process value falls<br />

below the setpoint.<br />

Sets the process value at which the relay toggles. The<br />

default value is different for each sensor.<br />

Sets the area for an amount of change necessary after the<br />

relay setpoint is reached in order to satisfy a condition.<br />

Sets a time period for de-activating an active relay if the<br />

process setpoint cannot be reached. Once an overfeed<br />

alarm is present, it must be manually reset.<br />

Sets a delay time for the relay to turn off (default:<br />

0 seconds).<br />

Sets a delay time for the relay to turn on (default:<br />

0 seconds).<br />

1 Deadband (Phase = Low) 6 Time (x-axis)<br />

2 Deadband (Phase = High) 7 ON delay (phase set high)<br />

3 Setpoint 8 OFF delay (phase set low)<br />

4 OFF delay (phase set high) 9 Source (y-axis)<br />

5 ON delay (phase set low)<br />

English 31