TeSys<br />

LUTM<br />

TeSys GV3L<br />

Circuit-breakers<br />

Motor control<br />

Controller for 3-phase motors<br />

MULTIFUNCTION protection<br />

1<br />

TeSys LC1D<br />

Contactor<br />

= +<br />

2<br />

3<br />

4<br />

Function characteristics Control base for use Multifunction<br />

with contactors<br />

control unit<br />

TeSys D (LC1D..) TeSys F (LC1F..) Class 5 to 35<br />

- Thermal overload protection against: LUTM10BL LUTM20BL LUCMT1BL<br />

short-circuit, overcurrent,<br />

phase failure or imbalance,<br />

insulation breaks (equipment only).<br />

- Manual, automatic or remote reset,<br />

- Thermal overload test function,<br />

- Overtorque and no-load running, alarm,<br />

- Motor operation log,<br />

- Motor parameters display on LUCM.., PC or HMI,<br />

- Integrated Modbus communication.<br />

ADVANCED protection<br />

5<br />

6<br />

7<br />

Function characteristics Control base for use Advanced<br />

with contactors<br />

control unit<br />

TeSys D (LC1D..) TeSys F (LC1F..) Class 10 Class 20<br />

- Thermal overload protection against: LUTM10BL LUTM20BL LUCBT1BL LUCDT1BL<br />

short-circuit, overcurrent,<br />

phase failure or imbalance,<br />

insulation breaks (equipment only).<br />

- Manual reset following thermal fault.<br />

- Thermal overload test function.<br />

8<br />

Current transformers<br />

9<br />

10<br />

Type of transformer<br />

Supply voltage<br />

24 V DC<br />

Operating current Primary 30 A 50 A 100 A 200 A 400 A 800 A<br />

Secondary<br />

1 A<br />

References LUTC0301 LUTC0501 LUTC01001 LUTC02001 LUTC04001 LUTC05001<br />

Above 32 A, the TeSys U controller provides a motor starter management system solution identical to that provided by the TeSys U starter-controller.<br />

Used in conjunction with a short-circuit protection device and a contactor, it provides a motor starter whose functions are the same as those of a TeSys U starter-controller<br />

and, in particular, provides the following functions: overload protection, motor starter control and application monitoring.<br />

It comprises a control unit, whose adjustment range is compatible with the secondary of current transformers, and a control base that also enables the fitting of a function module or<br />

communication module.<br />

It requires a 24 V DC external power supply.<br />

5/8<br />

Other versions: please consult our Customer Care Centre.