6.2.6 Connection of the Easymatic control or a<br />
room thermostat (option)<br />
The options are to be connected at the back of the<br />
control panel under the small flap.<br />
- Pivot the panel forwards after unscrewing the 2 fastening<br />
side screws.<br />
- Pull the small flap towards you <strong>and</strong> ensure that the<br />
connections are in accordance with the selected<br />
options.<br />
• Easymatic communicative remote control<br />
(box AD 136)<br />
- see the instructions delivered with the Easymatic<br />
remote control.<br />
• Programmable room thermostat<br />
(box AD 137)<br />
- remove the resistance from the Room Thermostat<br />
connector<br />
- connect, in any order, terminals 1 <strong>and</strong> 3 of the<br />
thermostat to the terminals of the Room Thermostat<br />
connector.<br />
- see also the instructions delivered with the thermostat.<br />
• Non-programmable room thermostat<br />
(box AD 140)<br />
- remove the resistance from the Room Thermostat<br />
connector<br />
- connect, in any order, terminals 1 <strong>and</strong> 4 of the<br />
thermostat to the terminals of the Room Thermostat<br />
connector.<br />
- see also the instructions delivered with the thermostat.<br />
Note : If a room thermostat with 2 dry-contact wires<br />
has been installed, it may be used.<br />
For this:<br />
- remove the resistance from the Room Thermostat<br />
connector<br />
- connect, in any order, the 2 thermostat wires to the<br />
terminals of the Room Thermostat connector.<br />
Remark:<br />
Connections can be with either a 2 wire telephone cable<br />
or an electrical section cable of up to 2 x 1,5 mm 2 .<br />
13<br />
BUS TAM<br />
SB<br />
BUS TAM SB<br />
1 2 3<br />
8666N094