9.6 Adjusting the minimum pressure<br />
Natural gas H <strong>and</strong> L, butane <strong>and</strong> propane.<br />
Adjust the pressure at the burner downstream of the<br />
gas assembly. The values to set are indicated in<br />
chapter 7.<br />
Measure the pressure at the boiler by connecting a<br />
pressure gauge to pressure offtake 17, as follows:<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
Remove the screw retaining the plastic cover.<br />
Remove the cover.<br />
Verify that the “maximum flowrate” plastic nut is<br />
screwed fully home.<br />
Force operation of the boiler at the minimum output<br />
setting by pressing the “clean” button E <strong>and</strong><br />
holding it down for 5 seconds (see section 4).<br />
Adjust the minimum pressure with the brass nut.<br />
- Turning the nut clockwise increases the<br />
pressure.<br />
- Turning the nut anti-clockwise<br />
reduces the pressure.<br />
After completing the adjustment, replace the<br />
cap.<br />
To revert to normal operation, press button E briefly.<br />
Disconnect the pressure gauge.<br />
Screw in the screw of the pressure offtake.<br />
Check for gas leaks.<br />
9.7 “Gas type” label<br />
Affix the label indicating the type of gas for which the<br />
boiler is equipped <strong>and</strong> set up.<br />