6.4 Fitting the boiler casing<br />
8666N092<br />
7. PRESSURE SETTING AND CALIBRATED INJECTOR AND DIAPHRAGM<br />
MARKINGS<br />
Equipment<br />
<strong>CITY</strong> <strong>1.24</strong> <strong>and</strong> <strong>2.24</strong><br />
Burner pressure <strong>and</strong> gas flow rate<br />
<strong>CITY</strong> <strong>1.24</strong> <strong>and</strong> <strong>2.24</strong><br />
ø<br />
mm<br />
Burner Natural gas H <strong>and</strong> L 1.35<br />
injectors Butane / Propane 0.8<br />
Diaphragm Natural gas H <strong>and</strong> L 5.2<br />
Butane / Propane 4.2<br />
Output nominal minimum<br />
Burner Nat. gas H mbar 6.5 1.0<br />
pressure Nat. gas L mbar 7.9 1.4<br />
Butane mbar 19.1 2.5<br />
Propane mbar 24.1 3.4<br />
Flow Nat. gas H m 3 /h 2.79 1.01<br />
rate * Nat. gas L m 3 /h 2.97 1.07<br />
Butane kg/h 2.08 0.75<br />
Propane kg/h 2.05 0.74<br />
15<br />
Note : fit the front panel after commissioning<br />
the boiler.<br />
* 1013 mbar at 15°C<br />
8666N093