1SDC200138F00012b) Time-delay device for under<strong>voltage</strong>release (D)The under<strong>voltage</strong> release can be combined with an electronictime-delay device for installation outside the <strong>circuit</strong>-breaker,allowing delayed trip unit tripping with adjustable preset times.Use of the delayed under<strong>voltage</strong> trip unit is recommended toprevent tripping when the power supply network for the trip unitis subject to brief <strong>voltage</strong> drops or power supply failures.Circuit-breaker closing is inhibited when it is not powered.The time-delay device must be used with an under<strong>voltage</strong> releasewith the same <strong>voltage</strong>.Reference figure in electrical <strong>circuit</strong> diagrams: YU +D (7)CharacteristicsPower supply (D):Adjustable opening time (YU+D):24-30 V DC48 V AC/DC60 V AC/DC110-127 V AC/DC220-250 V AC/DC0.5-1-1.5-2-3 s5<strong>ABB</strong> SACE 5/9