Switching and protection of capacitorsTable for selecting the protection andswitching <strong>circuit</strong>-<strong>breakers</strong> for capacitorsThe breaking capacity of the <strong>circuit</strong>-breaker must take into accountthe prospective short-<strong>circuit</strong> current at the point of installation.The available sizes are shown in the table.Rated current Rated current Overload Short-<strong>circuit</strong>Maximum power of the capacitor of the current of the capacitor protection protectionbank at 50Hz [kvar] Circuit-breaker transformer bank setting setting400V 440V 500V 690V Type In [A] Inc [A] I1 [A] I3 [A]578 636 722 997 E1 - E2 - E3 1250 834 1 x In OFF739 813 924 1275 E1 - E2 - E3 1600 1067 1 x In OFF924 1017 1155 1594 E2 - E3 2000 1334 1 x In OFF1155 1270 1444 1992 E3 2500 1667 1 x In OFF1478 1626 1848 2550 E3 - E4 - E6 3200 2134 1 x In OFFNoteThe E2L and E2L <strong>circuit</strong>-<strong>breakers</strong> are not suitable for switching capacitor banks.66/42<strong>ABB</strong> SACE