Example of selection of earth fault protection devices and theirrelevant settings.Switchboard A1600 kVA20 / 0,4 kVE3N25 with PR122In = 2500 AI4 = 0.25 x In = 625 At4 = 0.8 s (t=k)E1N12 with PR121In = 1000 AI4 = 0.2 x In = 200 At4 = 0.4 s (t = k)Switchboard BT4N320 with RC222In = 320 AT2N160 with RC221In = 100 AI Δn = 5 mAt Δn = 0.2 sI Δn = 0.1 mAt Δn = 0 s1SDC200199F00016<strong>ABB</strong> SACE 6/21