Primary and secondary distributionSelective protectionSelectivity is normally actuated for tripping overcurrent protectiondevices in civil and industrial installations to isolate thepart affected by a fault from the system, causing only the <strong>circuit</strong>-breakerimmediately on the supply side of the fault to trip.The example in the figure highlights the need to coordinatetripping between the two <strong>circuit</strong>-<strong>breakers</strong> A and B so that only<strong>circuit</strong>-breaker B is tripped in the event of a fault in C, ensuringcontinuity of service for the rest of the system supplied by<strong>circuit</strong>-breaker A.Whereas natural selectivity within the overload current range isnormally found due to the difference between the rated currentsof the load protection <strong>circuit</strong>-breaker and the main <strong>circuit</strong>-breakeron the supply side, selectivity can be obtained in the short<strong>circuit</strong>current range by differentiating the current values and, ifnecessary, the trip times.Circuit diagram with selectivecoordination of protections1SDC200181F0001Selectivity can be total or partial:– total selectivity: only <strong>circuit</strong>-breaker B opens for all currentvalues lesser than or equal to the maximum short-<strong>circuit</strong> currentin C;– partial selectivity: only <strong>circuit</strong>-breaker B opens for fault currentsbelow a certain value; A and B are both tripped forgreater or equal values.In principle, the following types of selectivity are possible:Current selectivity, obtainedby setting the instantaneoustrip currents of the <strong>circuit</strong>breakerchain to differentvalues (higher settings for the<strong>circuit</strong>-<strong>breakers</strong> on the supplyside). This often results inpartial selectivity.6Example of current-type selectivity1SDC200182F0001Time selectivity, obtained byintentionally incorporating increasingtime-delays in the triptimes of the <strong>circuit</strong>-<strong>breakers</strong> furthestto the supply side in thechain.Example of time-type selectivity1SDC200183F00016/2<strong>ABB</strong> SACE

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!