12.07.2015 Views

Emax Low voltage air circuit-breakers - ABB Download Center

Emax Low voltage air circuit-breakers - ABB Download Center

Emax Low voltage air circuit-breakers - ABB Download Center

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

1SDC200147F00015c) Electrical signalling of <strong>circuit</strong>-breaker racked-in/testisolated/racked outIn addition to mechanical signalling of the <strong>circuit</strong>-breaker position,it is also possible to obtain electrical signalling using 5 or10 auxiliary contacts which are installed on the fixed part.It is only available for withdrawable <strong>circuit</strong>-<strong>breakers</strong>, for installationon the fixed part.The auxiliary contacts take on the following configurations:– 5 contacts; set comprising 2 contacts for racked-in signal, 2contacts for racked-out signal, and 1 contact to signal thetest isolated position (main pliers isolated, but sliding contactsconnected).– 10 contacts; set comprising 4 contacts for racked-in signal, 4contacts for racked-out signal, and 2 contacts to signal thetest isolated position (main pliers isolated, but sliding contactsconnected).Reference figure in electrical <strong>circuit</strong> diagrams:S75I (31-32)S75T (31-32)S75E (31-32)51SDC200148F0001<strong>ABB</strong> SACE 5/13