Signal for overcurrent releases tripped4) Electrical signalling of electronicreleases trippedThe following signals are available after the electronic trip unithas tripped:4a) Electrical signalling of electronic trip units trippedThis allows remote signalling (electrical using switch) that the<strong>circuit</strong>-breaker is open following operation of the overcurrentreleases. The mechanical signalling pushbutton must berearmed to reset the <strong>circuit</strong>-breaker.Reference figure in electrical <strong>circuit</strong> diagrams: S51 (13)51SDC200144F00011SDC200141F00014b) Electrical signalling of electronic releases tripped withremote reset commandThis allows remote signalling (electrical using switch) that the<strong>circuit</strong>-breaker is open following operation of the overcurrentreleases. With this accessory, it is possible to reset the mechanicalsignalling pushbutton via an electrical coil from aremote command, which also allows the <strong>circuit</strong>-breaker to bereset.Available reset coils24-30 V AC/DC220-240 V AC/DC110-130 V AC/DCReference figure in electrical <strong>circuit</strong> diagrams: S51 (14)<strong>ABB</strong> SACE 5/11