Construction characteristicsOperating mechanismThe operating mechanism is of the stored energy type, operatedusing pre-charged springs.The springs are charged manually by operating the front leveror using a geared motor, supplied on request.The opening springs are charged automatically during the closingoperation.With the operating mechanism fitted with shunt closing andopening releases and the geared motor for charging the springs,the <strong>circuit</strong>-breaker can be operated by remote control and, ifrequired, co-ordinated by a supervision and control system.1➁ OPENING➀ CLOSING➀ OPENING➂ OPENING➁ CLOSING1SDC200020F00011SDC200021F0001The following operating cycles are possible without rechargingthe springs:– starting with the <strong>circuit</strong>-breaker open (0) and the springscharged:closing-opening– starting with the <strong>circuit</strong>-breaker closed (I) and the springscharged:opening-closing-opening.The same operating mechanism is used for the entire seriesand is fitted with a mechanical and electrical anti-pumpingdevice.<strong>ABB</strong> SACE 1/5