Reference Manual<br />

00809-0100-4804, Rev AA<br />

January 2011<br />

<strong>Rosemount</strong> <strong>3051S</strong> ERS System<br />

DP Calibration The DP calibration function can be used to adjust the calculated DP<br />

Fast Keys 3, 4, 2, 1<br />

measurement of the ERS system. For example, a DP zero trim can be<br />

performed if the calculated DP of the ERS system has a small offset when the<br />

expected output should be “0 DP.”<br />

NOTE<br />

Because the DP calculation is dependent on the P HI and P LO pressure<br />

measurements, all DP calibration functions should be performed after<br />

completing the calibration functions on the individual P HI and P LO sensors.<br />

While a lower or upper DP trim is not required, a zero DP trim should be<br />

performed after installing and calibrating the individual pressure sensors and<br />

before subjecting the ERS system to the actual process conditions in order to<br />

establish a zero-based DP measurement.<br />

DP Zero Trim<br />

The DP Zero Trim function establishes a true zero-based DP calculation by<br />

taking the current measurement output and forcing that value as the new<br />

zero-reference. A DP Zero Trim should only be performed when the expected<br />

output of the ERS system is “0 DP.” For non-zero based trims, a DP Lower<br />

Trim should be performed instead.<br />

The DP zero trim function requires both pressure sensors to be wired and<br />

connected.<br />

To perform a DP zero trim, follow the procedure below:<br />

1. Ensure that the individual PHI and PLO pressure sensors have been<br />

calibrated as detailed on page 4-3 and are wired together as shown in<br />

Figure 2-9, Figure 2-10, or Figure 2-11.<br />

2. Launch the “DP Zero Trim” function using AMS or a Field Communicator.<br />

3. Apply “0 DP” to the ERS System and wait for the DP measurement to<br />

stabilize.<br />

4. Using AMS or a Field Communicator, perform the zero trim function on<br />

the <strong>3051S</strong> ERS System.<br />

Upper and Lower DP Trims<br />

The DP calculation can be trimmed using a two-point calibration where lower<br />

and upper end-point pressures are applied, and all readings are linearized<br />

between the two points.<br />

Unlike the DP Zero Trim function, the Upper and Lower DP Trims can be<br />

performed when the ERS system is pressurized under actual process<br />

conditions.<br />

Always perform a lower DP trim first to establish the correct offset. The upper<br />

DP trim provides a slope correction.<br />

4-5