Table 5-1. Diagnostic Message<br />
Troubleshooting<br />
LCD display<br />
Message Host Diagnostic Message Possible Problems Recommended Actions<br />
CURR<br />
SAT<br />
DP<br />
ALERT<br />
FAIL<br />
BOARD<br />
ERROR<br />
FAIL<br />
PHI ERROR<br />
FAIL<br />
PLO ERROR<br />
FAIL<br />
THI ERROR<br />
FAIL<br />
TLO ERROR<br />
PHI ALERT<br />
P HI<br />
COMM<br />
ERROR<br />
P HI<br />
LIMIT<br />
P LO<br />
ALERT<br />
P LO<br />
COMM<br />
ERROR<br />
P LO<br />
LIMIT<br />
LOOP<br />
TEST<br />
SNSR<br />
COMM<br />
ERROR<br />
SNSR<br />
CONFIG<br />
ERROR<br />
mA Output Saturated The primary variable has exceeded the<br />
range points defined for the 4-20 mA<br />
analog output signal. The analog<br />
output is fixed at the high<br />
or low saturation point and is not<br />
representative of the current process<br />
conditions.<br />
System DP Alert The ERS system is measuring a<br />
differential pressure value that exceeds<br />
the configured upper or lower alert<br />
value.<br />
<strong>Electronic</strong>s Error The electronics featureboard in the<br />
ERS Primary Unit has malfunctioned.<br />
Verify the process conditions and modify the<br />
Analog Range Values if necessary.<br />
Verify the measured DP is beyond the trip limits.<br />
If necessary, modify the trip limits or disable the<br />
diagnostic.<br />
Replace the electronics featureboard.<br />
PHI Module Failure The PHI sensor module has failed. Verify the PHI Module Temperature is within the<br />
operating limits of the sensor. Replace the PHI sensor module if necessary.<br />
PLO Module Failure The PLO sensor module has failed. Verify the PLO Module Temperature is within the<br />
operating limits of the sensor. Replace the PLO sensor module if necessary.<br />
PHI Module Failure The PHI sensor module has failed. Verify the PHI Module Temperature is within the<br />
operating limits of the sensor. Replace the PHI sensor module if necessary.<br />
PLO Module Failure The PLO sensor module has failed. Verify the PLO Module Temperature is within the<br />
operating limits of the sensor. Replace the PLO sensor module if necessary.<br />
P HI Pressure Alert The P HI sensor module has detected a<br />
pressure value that exceeds the<br />
configured upper or lower alert value.<br />
P HI Module<br />
Communication Error<br />
Communication between the P-Hi<br />
sensor module and the electronics<br />
featureboard has been lost.<br />
PHI Pressure Out of Limits The PHI Pressure reading has<br />
exceeded the sensor’s maximum<br />
measurement range.<br />
PLO Pressure Alert The PLO sensor module has detected a<br />
pressure value that exceeds the<br />
configured upper or lower alert value.<br />
P LO Module<br />
Communication Error<br />
Communication between the P LO<br />
sensor module and the electronics<br />
featureboard has been lost.<br />
PLO Pressure Out of Limits The PLO Pressure reading has<br />
exceeded the sensor’s maximum<br />
measurement range.<br />
mA Output Fixed The analog output of the ERS System<br />
is in “fixed current mode” and is not<br />
representative of the HART PV.<br />
Sensor Module Missing A sensor module is missing or not<br />
detected.<br />
No P HI Module<br />
Configuration Present<br />
Neither of the modules in the ERS<br />
system are configured as the P HI<br />
sensor.<br />
Verify the measured PHI Pressure is beyond the<br />
trip limits. If necessary, modify the trip limits or<br />
disable the diagnostic.<br />
Verify the wiring between the PHI module and the<br />
electronics featureboard. Replace the PHI module and/or electronics featureboard if<br />
necessary.<br />
Check the process for potential overpressure<br />
conditions.<br />
Verify the measured PLO Pressure is beyond the<br />
trip limits. If necessary, modify the trip limits or<br />
disable the diagnostic.<br />
Verify the wiring between the PLO module and<br />
the electronics featureboard. Replace the PLO module and/or electronics featureboard if<br />
necessary.<br />
Check the process for potential overpressure<br />
conditions.<br />
Using a Field Communicator or AMS, disable<br />
“Loop Current Mode.”<br />
Verify that both sensors are connected and<br />
properly wired.<br />
Verify that both sensors are connected and<br />
properly wired. Change the pressure designation<br />
of one of the two modules to “P HI” using a Field<br />
Communicator or AMS.