ADDENDUM #1 Interior Masonry Chimney Conversions¥ Follow the requirements and use the equipment listed in the illustration to the right to install thisappliance into an interior masonry chimney.¥ Maximum vertical rise is 30Õ¥ Minimum vertical rise is 10Õ¥ Use the following restrictor positions:Position 2 for heights between 10Õ and 14ÕPosition 3 for heights between 14Õ and 22ÕPosition 4 for heights between 22Õ and 34ÕNOTE: these restrictor positions are based upon lab tests. The ideal restrictor position may vary slightly.The entire chimney systemmust be air-tight. Make sure toseal the flashing, clean-out,and thimble connection, and toinspect the chimney.Make sure the coaxial pipemaintains a 1Ó clearance to anycombustible. The vent must besealed air-tight.Co-AxialStraightLengths#990 90¡ Elbow#991 HighWindTerminationFlashing(included in#934 MasonryConversion KitHigh-Temp.Silicone#711 Flex Liner(4Ó dia.)(or other UL 1777Gas Liner)Connector withCover (includedin #934MasonryConversion Kit