Liquid chillers with axial fans<br />

IDENTIFICATION<br />

TECHNICAL DATA<br />

MODULO.RECIP.A.STD<br />

Modular air cooled packaged liquid chillers equipped with reciprocating compressor and axial fans.<br />

CoolingDensityPlus<br />

480kW in 6,5 m2 (DF = 74 kW/m2 ), the chiller with the highest Cooling Density (kW per m2 of<br />

space in plan) currently available in the market.<br />

MODULO.RECIP.A.STD - MODEL<br />

Cooling capacity (1) kW<br />

Compressors n.<br />

Gas circuits n.<br />

Dimensions Length mm<br />

Depth mm<br />

Height mm<br />

Net weight kg<br />

Mean sound pressure level (2) dB(A)<br />

MODULO.RECIP.A.STD - MODEL<br />

Cooling capacity (1) kW<br />

Compressors n.<br />

Gas circuits n.<br />

Dimensions Length mm<br />

Depth mm<br />

Height mm<br />

Net weight kg<br />

Mean sound pressure level (2) dB(A)<br />

220.S1 330.S1<br />

208 297,1<br />

1 1<br />

1 1<br />

2830 2830<br />

2300 2300<br />

2395 2395<br />

2700 2960<br />

77 78<br />

440.S1 550.S1<br />

396,5 478,4<br />

1 1<br />

1 1<br />

2830 2830<br />

2300 2300<br />

2395 2395<br />

3130 3300<br />

80 80<br />

(1) Data referred to chilled water temperature at 12/7°C; condenser air inlet at 35°C.<br />

(2) Mean sound pressure level 1m far from the unit in free field conditions, according to ISO 3744 norm.<br />

POWER SUPPLY: 400.3.50+N<br />

114 RC GROUP SpA • General Catalogue • 155.EN.0504