Heat pump liquid chillers with axial fans<br />

TECHNICAL DATA IDENTIFICATION<br />

REVERSO.SCROLL.A.P.STD “G”<br />

Heat pump air cooled packaged liquid chillers equipped with Scroll compressors and axial fans. Casing<br />

type: “G”.<br />

PerformancePlus<br />

PERFORMANCEPLUS system emphasizes the energy saving characteristics granted by IDEA patented software, proving<br />

REVERSO SCROLL heat pumps to be the most efficient solution currently available on the market from the point of view of the<br />

electric consumption.<br />

REVERSO.SCROLL.A.P.STD “G” - MODEL<br />

Size<br />

Cooling capacity (1) kW<br />

Heating capacity (2) kW<br />

Compressors n.<br />

Gas circuits n.<br />

Dimensions Length mm<br />

Depth mm<br />

Height mm<br />

Net weight kg<br />

Mean sound pressure level (3) dB(A)<br />

REVERSO.SCROLL.A.P.STD “G” - MODEL<br />

Size<br />

Cooling capacity (1) kW<br />

Heating capacity (2) kW<br />

Compressors n.<br />

Gas circuits n.<br />

Dimensions Length mm<br />

Depth mm<br />

Height mm<br />

Net weight kg<br />

Mean sound pressure level (3) dB(A)<br />

21.Z1 25.Z1 32.Z1 37.Z1 50.Z1 61.Z1<br />

G0 G0 G2 G2 G2 G4<br />

20,3 23,2 32,5 36,7 49,3 56,5<br />

23,6 26,6 35,6 42,2 55,4 66,9<br />

1 1 1 1 1 1<br />

1 1 1 1 1 1<br />

1150 1150 2000 2000 2000 2600<br />

895 895 1040 1040 1040 1200<br />

1640 1640 1690 1690 1690 1690<br />

350 350 500 560 610 770<br />

62 62 62 64 64 64<br />

36.Z2 42.Z2 50.Z2 64.Z2 74.Z2 87.Z2 100.Z2 124.Z2<br />

G2 G2 G2 G4 G4 G6 G6 G6<br />

34,2 39,7 44,6 57 68,4 86,3 96,1 112,3<br />

40,1 47,1 54,5 69,2 83,2 100,8 113 134,3<br />

2 2 2 2 2 2 2 2<br />

2 2 2 2 2 2 2 2<br />

2000 2000 2000 2600 2600 3600 3600 3600<br />

1040 1040 1040 1200 1200 1290 1290 1290<br />

1690 1690 1690 1690 1690 1690 1690 1690<br />

600 620 640 850 890 1210 1270 1270<br />

64 64 64 64 65 66 66 66<br />

(1) Data referred to outlet chilled water temperature at 7°C; air to condenser at 35°C.<br />

(2) Data referred to hot water temperature at 40/45°C; air to gas/air heat exchanger at 7°C with 90%RH.<br />

(3) Mean sound pressure level 1m far from the unit in free field conditions, according to ISO 3744 norm.<br />

POWER SUPPLY: 400.3.50+N<br />

184 RC GROUP SpA • General Catalogue• 155.EN.0504