Multifunction liquid chillers with axial fans<br />

IDENTIFICATION<br />

TECHNICAL DATA<br />

MULTIPLO.SCROLL.A.P.ELN “G”<br />

Multifunction air cooled packaged liquid chillers in extremely low noise equipped with Scroll compressors<br />

and axial fans. Casing type: ”G”.<br />

MULTIPLO: multifunction unit with total reclaim for simultaneous production of chilled and hot water for “comfort” and<br />

industrial applications in every climatic area.<br />

This series represents the ELN (Extremely Low Noise) range of this particular product.<br />

This product being particularly suitable for Hospitals, Health Centres and Hotels needs, ELN version represents the perfect<br />

solution to respect the requested acoustic parameters (often requested by law) for this kind of applications. RC ELN design<br />

keeps the easy installation and maintenance characteristics of the product, granting an acoustic and cooling performances<br />

durability in time.<br />

MULTIPLO.SCROLL.A.ELN “G” - MODEL<br />

Size<br />

Cooling capacity (1) kW<br />

Heating capacity (2) kW<br />

Cooling capacity (3) kW<br />

Heating capacity (3) kW<br />

Compressors n.<br />

Gas circuits n.<br />

Dimensions Length mm<br />

Depth mm<br />

Height mm<br />

Net weight kg<br />

Mean sound pressure level (3) dB(A)<br />

64.Z2 74.Z2 100.Z2 124.Z2<br />

G6 G6 G8B G8B<br />

56,8 63,6 87,6 107,1<br />

70,3 80,1 108 134<br />

59,5 69,4 94,6 114,9<br />

81,5 94,5 129,7 158,9<br />

2 2 2 2<br />

2 2 2 2<br />

3600 3600 5170 5170<br />

1290 1290 1290 1290<br />

1690 1690 1730 1730<br />

1060 1160 1485 1535<br />

54 56 56 57<br />

(1) Only cooling: Data referred to outlet chilled water temperature at 7°C; air to condenser at 35°C.<br />

(2) Only heating: Data referred to hot water temperature at 40/45°C; air to gas/air heat exchanger at 7°C with 90%RH.<br />

(3) Cooling and heating: Data referred to outlet chilled water temperature at 7°C; hot water temperature 40/45°C<br />

Mean sound pressure level 1m far from the unit in free field conditions, according to ISO 3744 norm.<br />