Free-cooling liquid chillers with axial fans - R134a<br />

TECHNICAL DATA IDENTIFICATION<br />

MAXIMO.SCREW.A.FLX “U”<br />

Air cooled packaged liquid chillers equipped with energy saving free-cooling SCR system, screw compressors<br />

and axial fans. Casing type: “U”.<br />

Serie FLX<br />

A range of highly FLeXible free-cooling chillers, to meet the most important requirements typical of modern<br />

plants, with a good quality/price/performance ratio.<br />

MAXIMO.SCREW.A.FLX “U” - MODEL<br />

Size<br />

Cooling capacity (1) kW<br />

Free-Cooling capacity (2) kW<br />

Compressors n.<br />

Gas circuits n.<br />

Dimensions Length mm<br />

Depth mm<br />

Height mm<br />

Net weight kg<br />

Mean sound pressure level (3) dB(A)<br />

440.V2 550.V2 610.V2 690.V2 765.V3 875.V3 1010.V3<br />

U9 U10 U10 U11 U12/11 U13/12 U14/13<br />

488,9 617,2 679,6 775,5 855,8 979,4 1136,4<br />

290,7 392,7 392,5 493,7 493,4 587,8 688,6<br />

2 2 2 2 3 3 3<br />

2 2 2 2 3 3 3<br />

4510 5500 5500 6490 7480 8470 9460<br />

2385 2385 2385 2385 2385 2385 2385<br />

2430 2430 2430 2430 2430 2430 2430<br />

5060 6310 6470 7400 8690 9760 10850<br />

75 76 76 77 77 77 77<br />

(1) Data referred to chilled water temperature at 15/10°C; outdoor air temperature at 35°C.<br />

(2) Data referred to inlet chilled water temperature at 15°C; outdoor air temperature at 2,5°C.<br />

(3) Mean sound pressure level 1m far from the unit in free field conditions, according to ISO 3744 norm.<br />

POWER SUPPLY: 400.3.50+N<br />

286 RC GROUP SpA • General Catalogue• 155.EN.0504