Air conditioners for information technology<br />

and communication - DISPLACEMENT<br />

IDENTIFICATION<br />

TECHNICAL DATA<br />

PEGASUS.DX.A.DL<br />

Direct expansion air conditioning units with remote air cooled condenser suitable for hi-tech. facilities and telecom<br />

exchanges. Air flow from the front or from the side through a grille for displacement air distribution. Thanks to<br />

“kit under” optional it is possible to convert the unit into a downflow air conditioning unit (under).<br />

SpaceSaver<br />

Displacement system eliminates the need for interspaces and ducts for the correct air distribution inside the rack.<br />

AIR CONDITIONERS<br />

PEGASUS.DX.A.DL - MODEL<br />

Size<br />

Cooling capacity (1) kW<br />

Air flow m 3 /h<br />

Compressors n.<br />

Dimensions Length mm<br />

Depth mm<br />

Height mm<br />

Net weight kg<br />

Noise pressure level (2) dB(A)<br />

REMOTE AIR COOLED CONDENSER<br />

TEAM.MATE.DX.A - MODEL<br />

Air flow m 3 /h<br />

Dimensions Length mm<br />

Depth mm<br />

Height mm<br />

Net weight kg<br />

Noise pressure level (3) dB(A)<br />

5.Z1 7.Z1 10.Z1 13.Z1 15.Z1 18.Z1 22.Z1 25.Z1<br />

S2 S2 S2 S4 S4 S4 S7/S S7/S<br />

5,9 7,6 10,6 13,5 16 18,4 23,1 26,3<br />

1700 2150 2450 4000 4650 4650 6300 7250<br />

1 1 1 1 1 1 1 1<br />

755 755 755 1105 1105 1105 1720 1720<br />

645 645 645 645 645 645 645 645<br />

1930 1930 1930 1930 1930 1930 1930 1930<br />

220 225 235 260 265 270 375 385<br />

53 55 57 57 59 59 59 61<br />

M.10 M.10 M.18 M.18 M.18 M.22 M.31 M.31<br />

3400 3400 4400 4400 4400 5600 10100 10100<br />

850 850 850 850 850 1150 1350 150<br />

482 482 482 482 482 482 620 620<br />

726 726 726 726 726 726 1026 1026<br />

31 31 37 37 37 47 95 95<br />

29,3 29,3 31,3 31,3 31,3 30,3 39,3 39,3<br />

(1) Performance referred to room conditions at 1m from floor at 24°C with 50% rH, deriving from the air conditioner air temperature inlet at 30°C with 35% rH;<br />

condenser air inlet at 35°C.<br />

(2) Noise pressure 1m far from the unit in free filed conditions.<br />

(3) Noise pressure 10m far from the unit in free filed conditions, condensing coils side.<br />

POWER SUPPLY: 230.1.50 from model 5.Z1 to model 8.Z1<br />

400.3.50+N from model 10.Z1 to model 25.Z1<br />

84 RC GROUP SpA • General Catalogue• 155.EN.0504