You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Heat pump liquid chillers with centrifugal fans<br />
IDENTIFICATION<br />
TECHNICAL DATA<br />
REVERSO.SCROLL.C.P.STD “G”<br />
Heat pump air cooled packaged liquid chillers equipped with Scroll compressors and centrifugal fans.<br />
Casing type: ”G”.<br />
REVERSO SCROLL represents the latest generation of heat pump liquid chillers with IDEA patented dynamic defrosting system<br />
and combines current SCROLL technology with RC 40-year experience to grant investment durability in time.<br />
CENTRI version, whose condensing section is equipped with centrifugal fans, allows the use of REVERSO liquid chillers even in<br />
INDOOR installations.<br />
REVERSO.SCROLL.C.P.STD “G” - MODEL<br />
Size<br />
Cooling capacity (1) kW<br />
Heating capacity (2) kW<br />
Compressors n.<br />
Gas circuits n.<br />
Dimensions Length mm<br />
Depth mm<br />
Height mm<br />
Net weight kg<br />
Mean sound pressure level (3) dB(A)<br />
REVERSO.SCROLL.C.P.STD “G” - MODEL<br />
Size<br />
Cooling capacity (1) kW<br />
Heating capacity (2) kW<br />
Compressors n.<br />
Gas circuits n.<br />
Dimensions Length mm<br />
Depth mm<br />
Height mm<br />
Net weight kg<br />
Mean sound pressure level (3) dB(A)<br />
21.Z1 25.Z1 32.Z1 37.Z1 50.Z1 61.Z1<br />
G1 G1 G1 G3 G3 G3<br />
18,9 21,4 28,6 34,9 46,2 55,6<br />
22,8 26,1 34,3 41,1 53,8 66,3<br />
1 1 1 1 1 1<br />
1 1 1 1 1 1<br />
1150 1150 1150 2000 2000 2000<br />
895 895 895 1040 1040 1040<br />
1960 1960 1960 2010 2010 2010<br />
410 410 455 690 760 780<br />
59 59 66 60 68 68<br />
36.Z2 42.Z2 50.Z2 64.Z2 74.Z2 87.Z2 100.Z2 124.Z2<br />
G3 G3 G3 G3 G5 G7 G7 G7<br />
32,3 37,5 42,5 56 68,4 82,7 91,4 109,6<br />
38,7 45,7 52,2 68,5 83,2 96,5 107,6 132,6<br />
2 2 2 2 2 2 2 2<br />
2 2 2 2 2 2 2 2<br />
2000 2000 2000 2000 2600 3600 3600 3600<br />
1040 1040 1040 1040 1200 1290 1290 1290<br />
2010 2010 2010 2010 2240 2010 2010 2010<br />
720 740 750 820 1090 1480 1540 1570<br />
59 60 64 68 70 69 69 69<br />
(1) Data referred to outlet chilled water temperature at 7°C; air to condenser at 35°C.<br />
(2) Data referred to hot water temperature at 40/45°C; air to gas/air heat exchanger at 7°C with 90%RH.<br />
(3) Mean sound pressure level 1m far from the unit in free field conditions, according to ISO 3744 norm.<br />
POWER SUPPLY: 400.3.50+N<br />
210 RC GROUP SpA • General Catalogue• 155.EN.0504